SEW變頻器MOVITRAC-31C系列故障代碼

發布時間:2019-08-02 15:34:55來源:

錯誤代碼 型號 品牌 錯誤類型 錯誤原因 解決辦法
1 MOVITRAC-31C SEW Overcurrent Short circuit/earth fault at the output.Motor too large.Faulty output stage. Remove short-circuit.Connect smaller motor.If fault can still not be reset,contact SEW service.
2 MOVITRAC-31C SEW DC link voltage DC link voltage too high. Increase deceleration ramps.
3 MOVITRAC-31C SEW Brake chopper Regenerative power too highBraking resistor circuit interruptedShort-circuit in the brakingresistor circuitBraking resistance value too highFaulty brake chopper Increase deceleration ramps.Check connecting leads of thebraking resistor.Check technical data of thebraking resistor.Exchange MOVITRAC® 31C
5 MOVITRAC-31C SEW Regenerativeoverload With active regen. n monit. (P520/P522)and speed control (P770):faulty encoder signalswrong number of pole pairs (P324/P344)value of increments (P773) not correct Check encoder.Check encoder connection.Set number of pole pairs correctly.Set value of increments correctly.
4 MOVITRAC-31C SEW Cont. overload ´t utilization too high (> 125(%)). Reduce load.
6 MOVITRAC-31C SEW Overtemperature Thermal overload of the inverter. Reduce load and / or ensure adequatecooling.
7 MOVITRAC-31C SEW Phase failure With active mains volt. monitor.(P530)Phase missing at TL. X1:1/2/3. Check mains supply.
10 MOVITRAC-31C SEW Direction ofrotation Only with active speed control (P770):Encoder tracks A/A and B/B areswapped in pairs.Motor rotates in opposite direction.Regen. overload (i.e. with sagging hoist)because of excessive load or BOOSTsetting too low (P321/P341). Check encoder connection.Exchanging two motor phases.Reduce load or increase BOOST.
11 MOVITRAC-31C SEW Speeddetection Only with active speed control (P770):Faulty encoder connection.FEN31C/FPI31C option not installed. Check encoder connection.Insert correct option(FEN31C or FPI31C).
12 MOVITRAC-31C SEW Mot. overload With active n monit. (P510/P512)and speed control (P770):faulty encoder signalswrong number of pole pairs (P324/P344)value of increments (P773) not correct Check encoder.Check encoder connection.Set number of pole pairs correctly.Set value of increments correctly.
13 MOVITRAC-31C SEW Startingconditions With active hoist function (P710/P712):Current too low during the premagnetizationphase:Motor rated power selected too smallin relation to the inverter rated power.Cross-section of the motor leads toosmall. Check startup data and carryout new startup if necessary.Check inverter-motor connection.Check cross-section of the motorleads and increase if necessary.
14 MOVITRAC-31C SEW Output open With active hoist function (P710/P712):Two or all output phases interrupted.Motor rated power selected too smallin relation to the inverter rated power. Check inverter-motor connection.Check startup data and carryout new startup if necessary.
17 MOVITRAC-31C SEW Stack overflow Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
18 MOVITRAC-31C SEW Stack underflow Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
19 MOVITRAC-31C SEW NMI trap Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
20 MOVITRAC-31C SEW Undefinedopcode Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
21 MOVITRAC-31C SEW Protected instr. Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
22 MOVITRAC-31C SEW Word op.access Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
23 MOVITRAC-31C SEW nstruct. access Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly,
24 MOVITRAC-31C SEW Ext. bus access Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
25 MOVITRAC-31C SEW EEPROM Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
26 MOVITRAC-31C SEW No connection Inverter electronics faulty.Possible cause: EMC effect. The notes for EMC compliant installationmust be observed.The reset for error 25 consists ofseveral steps:1. Factory setting (P830 = YES)2. Re-set matched parameters3. Carry out resetIf fault occurs repeatedly, contactSEW service.
27 MOVITRAC-31C SEW Ext. terminal External fault signal has appeared at a programmableinput Eliminate the cause of the fault. Reprogramthe terminal, if necessary
28 MOVITRAC-31C SEW FaultINTERBUS FFI31C and control mode (P841) = Fieldbus:Faulty monitoring signal. Check Fieldbus connection.
32 MOVITRAC-31C SEW Copying Only when copying the parameters (P820):Break or interference in PC or FBG31Cconnection. Check connection between inverter andPC. Remove FBG31C keypad and plugagain.
33 MOVITRAC-31C SEW Master-slave Connection master-slave is interrupted.0V5 connection (RS-485) missingMaster or slave defined incorrectlyin P880. Check master-slave connection.0V5-establish connection betweenmaster and slaveSet P880 correctly.
34 MOVITRAC-31C SEW Fieldbustimeout No communication between master andslave within the specified time of theresponse monitoring. Check communication routine of themaster.Increase fieldbus timeout time (P571)/deactivate monitoring.
35 MOVITRAC-31C SEW ConnectionEncoder-FRS Encoder connection faulty.Power supply of the encoder faulty. Check encoder connection.Check power supply of the encoder.
36 MOVITRAC-31C SEW ConnectionMaster-slave Only with FRS and cable break master-slave(P557) = YES:Setpoint connection of slave (TL. 98-101)is disrupted.Master Speed 0 ® slave FRS CTRLis disrupted.Slave FRS CTRL input not assigned.Master Speed 0 output not assigned.No master inverter available.Encoder < 512 pulses per revolution used. Check installation.Check programming of the binaryinputs and binary outputs.Check if encoder type is correct.
37 MOVITRAC-31C SEW FRS RAM fault Internal fault. If fault occurs repeatedly, contactSEW service.
38 MOVITRAC-31C SEW FRS processdata fault Fault on interface between inverter andFRS. If fault occurs repeatedly, contactSEW service.
39 MOVITRAC-31C SEW FRS parameterdata fault Invalid value for FRS parameters (P55_). Check parameter settings.
41 MOVITRAC-31C SEW FRS lag fault Polarity of the encoder not set correctly.Acceleration ramps too short.P-gain of the positioningcontroller too smallSpeed controller not set property.Value for lag error tolerance too small Change polarity of encoder.Increase ramps.Increase P-gain.Select new parameters forspeed controller.Increase lag error tolerance (P551).Check wiring of encoder, motor andmains phases.Check if mechanical system is sluggishor whether drive hit an obstacle.
43 MOVITRAC-31C SEW Faultbinary output Load on TL. X3:61 > 150 mA.Load on the otherbinary outputs > 50 mAShort circuit on binary output.Capacitive load on binary output. Check installation of the binary outputs.

SEW變頻器維修MOVITRAC-31C系列  15515598858  0371-56700815

用手機看
SEW變頻器MOVITRAC-31C系列故障代碼

拍下二維碼,信息隨身看

試試用手機掃一掃,
在你手機上繼續觀看此頁面。

主站蜘蛛池模板: 天天摸日日干| 男人狂躁戳女人下免费看| 五月激情久久| www久久com| 亚洲第一中文字幕| 国产福利精品一区二区| 欧美福利网站| 一区 在线播放| 成人入口| 国产精亚洲视频| 美女网站黄| 日本综合欧美一区二区三区| 一区精品麻豆入口| 中文字幕黄色| 性夜影院爽黄e爽痛轻点www| a男人的天堂久久a毛片| 加勒比在线一区| 铃原爱蜜莉福利一区在线观看| 亚洲一区二区免费看| 婷婷综合久久| 91精品国产品国语在线不卡| 99久久精品一区二区三区| 激情综合网五月激情| 久久精品中文字幕免费| 婷婷色在线视频| 亚洲 图片 小说 欧美 另类| 91精品国产福利尤物| 日本精品一区二区三区在线观看 | 国产欧美激情一区二区三区| 欧美黄色免费大片| 日韩视频免费| 日日摸夜夜添夜夜添毛片| 视频一区亚洲| 色多多免费观看| 色老大综合久久综合热| 在线播放亚洲视频| 97影院理论午夜论不卡| 国产精品网站 夜色| 国产精品久热| v视界影院视频一区二区三区| 丁香六月 久久久|